Product Details:
Place of Origin: Nanjing,China
Brand Name: TOKEN
Certification: CE;ROHS
Model Number: TKC-TG352 series
Payment & Shipping Terms:
Minimum Order Quantity: 10pcs
Price: Price reconsideration
Packaging Details: Little carton:34*23*21CM 36pcs/carton;Large carton size 48*37*26CM 72pcs/carton
Delivery Time: 7~10 working days
Payment Terms: L/C, T/T, D/P, Western Union
Supply Ability: 10K pcs per month

Open Loop Programming Hall Effect Current Transformer

Description
Product Name: Open Loop Current Sensor Theory: Hall Sensor
Power Supply: +5V Input Current: 20-500A
Offset: 1/2VCC Standards: UL94-V0
High Light:

Programming Hall Effect Current Transformer

,

Open Loop Hall Effect Transmitter

,

500A Hall Effect Current Transformer

20-500A Hall Effect Current Sensor Transducer Programming Type

 

 

Characteristics chart

 

The TKC-TG3 series current sensor is a open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of 3 phase DC, AC or pulsed currents.

 

Electrical data(Ta=25℃±5℃,RL=2KΩ,CL=10000PF)

 

Type

Parameter

TKC

20TG352

TKC

50TG352

TKC

100TG352

TKC

200TG352

TKC

300TG352

TKC

400TG352

TKC

500TG352

Unit

 

Rated current(Ipn)

±20 ±50 ±100 ±200 ±300 ±400 ±500 A

 

Measuring range(Ip)

±22 ±55 ±110 ±220 ±330 ±440 ±550 A
Rated output @Ip=±Ipn ±2±1%       V
Supply voltage +5 ±5%       V

Power Consumption

15       mA

Offset voltage

±20       mV

Magnetic offset

±15       mV

 

Offset drift

@ -40~+85℃ ≤±2.0       mV/℃
output drift ±1.0       mV/℃

 

Linearity

@Ip=0-±Ipn ≤1       %FS

Response time

@50A/μS, 10%-90% ≤8       μS
Galvanic isolation @ 50HZ,AC,1min 2.5       KV

 

 

Applications

 

Variable speed drives

Welding machine

Battery supplied applications

Uninterruptible Power Supplies (UPS)Electrochemical

 

Mechanical dimension(for reference only)

 

Open Loop Programming Hall Effect Current Transformer 0

 

Open Loop Programming Hall Effect Current Transformer 1

 

Remarks:

1. All dimensions are in mm.

2. General tolerance ±1mm

 

Directions for use

 

Is will be in a forward direction when the Ip flows according to the direction of the arrowhead.

 

The primary conductor should be≤120℃.

 

The dynamic performance (di/dt and the response time) is the best when the primary hole is fully filled with the bus bar.

 

 

Standards

 

  • UL94-V0.
  • EN60947-1:2004
  • IEC60950-1:2001
  • EN50178:1998
  • SJ 20790-2000

 

General date

 

  Value Unit Symbol
Operating temperature -40 to +125 ºC TA
Storage temperature -40 to+150 ºC TS
Mass(approx) 99 g M

 

 

Characteristics chart


Open Loop Programming Hall Effect Current Transformer 2

 

 

 

 

 

 

 

Contact Details
Nanjing Token Electronics Science&Technology Co., Ltd.

Contact Person: Ms. Suki

Tel: 13951079826

Fax: 86-025-84643985

Send your inquiry directly to us (0 / 3000)